Reviewed equipment commands

Declare commands in Designer → Project tools → Equipment commands, then place an Equipment command control and select a declaration. Definitions travel with saved project drafts, packages and the complete application publication. Designer Preview never dispatches commands; testing uses the published operator application.

Every command specifies a concrete configured memory or OPC UA tag, scalar type, readable confirmation text and optional separate readback tag. Numeric commands require minimum and maximum limits. Text commands have a bounded maximum length. Readback defaults to the written tag, with a 100–10,000 ms deadline and optional nonnegative numeric tolerance. The target, readback and command types must match. Derived expression tags and disabled providers, scan groups, instances, tags or connections cannot be commanded.

Operator workflow

  1. Enter a requested value and choose Review command. The gateway checks the current publication, command permission, types, limits and configuration, then reads the current target value.
  2. Review current/requested values and the authored confirmation. The review token is bound to the account revision, project and command, expires in 30 seconds, and can dispatch only once.
  3. Choose Confirm command. The gateway rejects changed publication/configuration/value or a concurrent in-flight command to the same tag. It records an audit attempt before dispatch.
  4. The gateway sends one write and reads the configured feedback until it matches or the deadline expires. The response distinguishes confirmed, rejected, notConfirmed and uncertain. A lost response never implies success or a safe retry. Use the correlation reference to inspect the audit.

Commands is a separate project permission. Existing View or Operate grants do not authorize device writes. Gateway administrators have it; other accounts need an explicit grant under Gateway Settings → Security and readable tag scopes covering both target and readback. Commands includes Operate and View. Operator mutations also require the authenticated operator session and CSRF token. Revoked/changed accounts cannot use an old reviewed intent; permission and tag access are rechecked immediately before dispatch.

Confirmation and readback are application controls, not PLC interlocks. Fresh-value comparison is not an atomic compare-and-write operation on the device. An external controller or client can change the device after that comparison. Readback confirms a sampled value, not completion of a physical action. Protocol/application timeouts cannot undo a write already received by equipment. OPC UA writes are never automatically retried.

Ordinary Python system.tag.writeBlocking retains its memory-tag scope; it does not bypass this equipment-command contract. Commands currently use the explicit operator control/API; there is no implicit write from a bound input, and no momentary/pulse automation.

API

The project API exposes GET /runtime/commands?publishedAt=... to viewers. POST /runtime/commands/{id}/review takes { publishedAt, value }. POST /runtime/commands/{id}/execute takes { token, confirmed: true }. Review/execute require Commands permission. No client-supplied endpoint, node ID or script is accepted. The actual OPC endpoint and node are resolved from gateway-owned tag configuration.

Pending reviews are bounded to eight per account and 128 gateway-wide. A process restart invalidates them. No durable command replay is attempted. Audit records identify actor, project, command, correlation ID and outcome without logging submitted values or connection credentials. A receipt applies to that invocation, not a permanently synchronized browser field.

Synthetic workshop

examples/equipment-commands.json and tools/load-equipment-commands-example.mjs create three independent memory tags under [default]CommandWorkshop. They do not configure an OPC endpoint or write physical equipment. Run the loader against an isolated local gateway using SPARKSTUDIO_ADMIN_AUTH_FILE; add --publish to deliberately publish. The loader rejects colliding project names/tag paths.

Review and confirm a speed, run flag and note. Verify the separate live displays. Try an out-of-range speed, cancel confirmation, change a value from another operator after review, and compare an Operate-only account with one granted Commands. Review the audit references. Re-export/import retains declarations and controls, but the imported project has no publication or gateway tags.

An independently hosted loopback OPC UA simulator validates protocol writes separately from memory command checks. Deployment to an identified test device, process interlocks, external-client races and production load remain site acceptance work.

Verification: dotnet run --project src/SparkStudio.Gateway.Tests -- --equipment-commands-only covers intent ownership/replay, bounds, expiration, stale state/configuration/publication, permission revocation, cancellation before and after dispatch, concurrent command refusal and bounded readback. dotnet run --project src/SparkStudio.Connectors.Tests -- --opc-integration checks real loopback OPC UA accepted/rejected writes and readback. With the owned 5093 fixture running, set SPARKSTUDIO_TEST_AUTH_FILE to its ignored browser-auth.json and run node tools/test-equipment-commands.mjs for authenticated command/scoping/CSRF/audit and authored workshop re-export checks.