Alarms and retained history

Open Gateway Settings → Alarms & history with the gateway Configuration capability. Add alarm conditions and historical tags using their typed fields. New rules start disabled. Save configuration applies the complete revision; Cancel changes restores the last loaded configuration. A concurrent edit is rejected so one administrator cannot silently overwrite another's changes.

An alarm names a resolved tag, a high/low/equal condition, setpoint, absolute deadband and priority 1–4. High activates at or above its setpoint and clears below setpoint minus deadband; Low is the reverse. Equal activates at the exact setpoint and remains active within its deadband. Bad-quality samples preserve an existing active state and show their quality. Disabling a rule clears its active state.

Add Alarm Status Table, Alarm Journal Table and Historical Trend to operator screens through the component palette. Their properties remain in the property grid. Status and journal visibility follow the project's tag scope. Acknowledgement requires Operate permission and identifies the exact occurrence; an old acknowledgement cannot acknowledge a newer alarm. Acknowledgement and clearing are separate states. No external notification delivery is configured. Journal responses include events and truncated. Both the requested visible-row limit and the 10,000-entry bounded global scan can make a result incomplete. The runtime shows that disclosure even when unrelated activity exhausts the scan before any event visible to the current project is found. Changing an alarm's source, condition, deadband or enabled state closes the prior occurrence with a reconfigured journal entry; the next active occurrence needs its own acknowledgement. SQLite stores the applied definition identity, so a restart or retry after an interrupted configuration save completes reconciliation before showing healthy state. An enabled numeric condition receiving a nonnumeric value reports Bad_TypeMismatch, preserving an existing active alarm rather than silently clearing it.

History records value changes beyond the configured absolute deadband, quality changes and a periodic sample at the maximum interval (250 ms through one day). Retention is 1–3650 days. Trends query bounded raw samples over at most 31 days, up to 32 paths and 10,000 points per path, and disclose truncated results. These are stored samples, without interpolated aggregates, redundant collectors or store-and-forward to an external historian.

The gateway stores rule configuration in process-data.json and operational state/journal/history in process-data/journal.sqlite under its data directory. Back up operational data through the stopped-gateway recovery procedure; an online configuration backup does not promise to include retained history.

Changing retention prunes expired samples immediately when configuration is saved, including disabled rules. Removing a rule stops collection while keeping its last retention policy until its remaining samples expire. Legacy orphan paths without a saved policy receive a bounded seven-day policy.

An invalid configuration or unavailable recording database leaves the gateway running with an explicit diagnostic fault; runtime reads fail instead of reporting an empty healthy history. The settings editor offers a recovery draft for invalid configuration. Review it and confirm replacement before saving: the original bytes are preserved as process-data.json.invalid-*.json first. Database faults require repairing permissions or recovering the database and restarting the gateway; saving rules never deletes or silently recreates a corrupt database.

Synthetic workshop

The source example is process-data-workshop.json. It requires gateway setup and therefore is listed separately from the portable .sparkproj collection. It uses one independently authored Double memory tag; there is no device or external database connection.

  1. Use an isolated development gateway. Set SPARKSTUDIO_ADMIN_AUTH_FILE to a protected local JSON credential file and run node tools/load-process-data-example.mjs http://127.0.0.1:5091. The loader rejects existing project/tag/rule identities before adding anything.
  2. Open Alarms and history workshop, inspect it and explicitly Publish. The loader leaves the draft unpublished unless --publish is supplied. Grant the operator View, Commands and Operate, and allow [default]ProcessWorkshop/ in any configured project tag scope.
  3. In Gateway Settings, stage a changed deadband and choose Cancel. The saved revision must be unchanged. Use Save only for the intended configuration.
  4. In the operator application, review and confirm temperature 90. The High alarm activates. Acknowledge it and compare a second operator tab. The numeric setpoint input and command button use the same reviewed equipment command. Committing the numeric input opens confirmation before writing.
  5. Set 78: the five-degree deadband keeps High active. Set 74: it clears. Set 10 to activate Low and 23 to clear it. Inspect the timestamped journal and trend samples. Commands change only this synthetic memory tag.
  6. Restart only the isolated gateway. Reopen the application and verify retained acknowledgement/journal/history. Compare View-only access, which cannot acknowledge or issue commands, and a tag scope excluding the workshop.

The setup loader adds configuration and a project in separate guarded requests. It is not an all-resource transaction. If a request fails, inspect the named workshop resources before retrying; it never deletes pre-existing resources. Remove the synthetic project and disable its rules when finished. Generated packages remain under artifacts/sparkproj/; no live gateway export belongs in Git.